The parameters have the following meaning:
Parameter
Description
L1
No monitoring of power supply 1
L2
No monitoring of power supply 2
If you do not select any parameters from the parameter list, the default value "L1 and L2" is
used.
Result
The setting for monitoring the power supplies is configured.
Further notes
You can display the current setting with the
show events faults config
command.
You enable the function with the
power
command.
12.1.8.10
link
Description
With this command, you configure and enable the monitoring of the physical network
connections for cable breaks or for pulling of the connector.
Requirement
You are in the EVENTS configuration mode.
The command prompt is as follows:
cli(config-events)#
Syntax
Call up the command with the following parameters:
link {up|down}[{<interface-type><interface-id>}]
The parameters have the following meaning:
Parameter
Description
Range of values / note
up
Only the establishment of a connection
is signaled
-
down
Only a break on a connection is signaled -
interface-type
Type or speed of the interface
Enter a valid interface.
interface-id
Module no. and port no. of the interface
For information on names of addresses and interfaces, refer to the section "Addresses and
Diagnostics
12.1 Event and fault handling
SCALANCE XB-200/XC-200/XF-200BA/XP-200/XR-300WG Command Line Interface
Configuration Manual, 07/2017, C79000-G8976-C361-06