4.4.2.1
signaling contact mode
Description
With this command, you specify the reaction of the signaling contact.
Requirement
You are in the Global configuration mode.
The command prompt is as follows:
cli(config)#
Syntax
Call up the command with the following parameters:
signaling-contact mode {conventional | aligned}
The parameters have the following meaning:
Parameter
Description
conventional
An error/fault is displayed by the fault LED and the signaling contact is
opened. When the error/fault state no longer exists, the fault LED goes off
and the signaling contact is closed.
aligned
The way the signaling contact works does not depend on the error/fault that
has occurred. The signaling contact can be opened or closed as required by
user actions.
Result
The reaction of the signaling contact is specified.
Further notes
You display the setting with the
show signaling contact
command.
4.4.2.2
signaling-contact status
Description
With this command, you close or open the signaling contact.
Requirement
You are in the Global configuration mode.
The command prompt is as follows:
Functions specific to SCALANCE
4.4 Signaling contact
SCALANCE XB-200/XC-200/XF-200BA/XP-200/XR-300WG Command Line Interface
140
Configuration Manual, 07/2017, C79000-G8976-C361-06