Operating Instructions
Part Two- Manipulating the Moveable Drawout Element
Unlocked Position to Test Position
Racking the moveable drawout element from the unlocked
position to the test position engages the moveable drawout
element with the stationary drawout element. The physical
position of the moveable drawout element will be un
changed .
To rack the moveable drawout element from the unlocked
position to the test position:
NOTE:
If
extension rails are pulled out, push them in
until they hit a solid stop.
1 .) Set the directional shift lever to the racking-in position;
2.) Pull the interlock lever down to the interlock disengaged
position. (Illustrated beneath padlock device.) If the breaker
contacts are closed, pulling the interlock lever down Will tnp
the breaker
3.)
Pump the racking pump handle until the moveable drawout
element has reached the test position.
4.) When the moveable drawout element reaches the test
position, the interlock lever will automatically return to the
interlock engaged position, the racking pump handle can
not be pumped, and the position indicator will display that
the moveable drawout element is in the test position.
Stab
Finger
Cluster
Test
Stab
Finger
Cluster
Unlocked
Relative position of finger clusters to bus stabs.
t
23
www
. ElectricalPartManuals