9-104
System Manual
C79000-G8576-C199-06
However, analog input modules and analog output modules may be given the
same address with cyclic sampling because they are distinguished by the user
program. This is not possible with selective sampling.
For cyclic sampling, you can address the module in the address range from 0
to 255, and for selective sampling from 128 to 255. For selective sampling,
you can also use the address range from 0 to 127 after appropriate
programming in DB 1 of the user program.
Example:
On an analog output module with 8 outputs with start address 144 (IB 144 =
output byte 144), output channel 7 is to be scanned by the program.
Step
Action
1
Affix the self-adhesive label with address 160 on the free field under the
addressing switch on the module. ADB 4 and ADB 7 are marked on the
label.
2
Press the appropriate rockers of the addressing switch down on the side
marked by a dot on the module cover. Set the other rockers to the opposite
setting. This sets the start address of the module.
ADB 4 and ADB 7 results in 2
4
+ 2
7
= 16 + 128 = 144
3
Enter the address 144 + 7 x 2 = 158 in the program for input channel 7.
Addressing for
Cyclic/Selective
Sampling
Analog Input/Output Modules
Summary of Contents for S5-135U
Page 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Page 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Page 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Page 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Page 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Page 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...