![Siemens S5-135U System Manual Download Page 356](http://html.mh-extra.com/html/siemens/s5-135u/s5-135u_system-manual_377341356.webp)
8-44
System Manual
C79000-G8576-C199-06
8.4.7
6ES5 436-4UA12 Digital Input Module
Rated input voltage
115 to 230 V AC (47 to 63 Hz)
Number of inputs
16
Isolation
Yes, 2 groups of 8 inputs
Input voltage
for logic 0
for logic 1
0 to 60 V AC
90 to 264 V AC
Rated input current
at 115 V AC
at 230 V AC
15 mA typical
25 mA typical
(2-wire-BERO can be connected)
Input frequency
20 Hz max. as pulse train
Delay time
for positive-going edge
for negative-going edge
5 ms typical (2 to 15 ms)
20 ms typical (10 to 25 ms)
Input resistance
10 kilohms typical
Coincidence factor (total load capability)
ventilated
not ventilated
100 %
75 % at 230 V AC;
100 % at 35
o
C;
100 % at 115 V AC
Permissible line length
600 m max. unshielded
1000 m max. shielded
Power supply
Digital section from system bus
5 V, 100 mA typical
Power dissipation (rated operation)
3.5 W at 115 V, 17.0 W at 230 V
Enable input (F+/F–)
Jumper in front connector
Voltage test to VDE 0160
Between two groups: 2000 V AC;
Between group and ground point: 1500 V AC
Mechanical specifications
Dimensions (W x H x D)
40 mm x 255 mm x 195 mm
Weight
Approx. 0.55 kg
Digital Input/Output Modules
Summary of Contents for S5-135U
Page 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Page 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Page 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Page 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Page 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Page 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...