6-7
System Manual
C79000-G8576-C199-06
16
1
EP 7
EP 60
9
8
8
9
1
16
When the unit is delivered, all communication flag areas are activated
(see above):
On Coordinator A
by jumpers at EP 7
On Coordinator C
by jumpers at EP 60
Jumper
Comm. Flag Byte
Address
8 - 9
7 - 10
6 - 11
5 - 12
4 - 13
3 - 14
2 - 15
1 - 16
0 to 31
32 to 63
64 to 95
96 to 127
128 to 159
160 to 191
192 to 223
224 to 255
F200H to F21FH
F220H to F23FH
F240H to F25FH
F260H to F27FH
F280H to F29FH
F2A0H to F2BFH
F2C0H to F2DFH
F2E0H to F2FFH
Jumper inserted:
area activated (coordinator
acknowledges in this area)
Jumper not inserted:
area masked out (coordinator
does not acknowledge in this area)
You wish to mask out the four communication flag areas with the highest
addresses on COR A:
1
8
9
16
EP7
Address F200H to F27FH
Activated (Jumper Inserted)
Address F280H to F2FFH
Masked Out (Jumper Open)
Figure 6-3
Example of Addressing the Communication Memory on COR A
Examples
Multiprocessor Operation/Coordinators
Summary of Contents for S5-135U
Page 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Page 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Page 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Page 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Page 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Page 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...