9-52
System Manual
C79000-G8576-C199-06
You must observe the following when configuring systems:
Switching on
At the latest 100 ms after power-up of the PLC, the voltage
must be present at the enable inputs of the I/O modules.
Switching off
When the PLC has been switched off, the voltage at the
enable inputs of the I/O modules must still be present as
long as the internal 5 V voltage is present.
You should observe the following instructions for switching off CCs and
equipment for supplying power to the enable inputs.
When there is a need to switch off the load power supply separately without
affecting the enabling of modules, there are the following possibilities for
producing the enable voltage. These exist even when the load power supply
is used without an additional capacitor and common shutdown.
230 V AC supply for CC/EU and load power supply
F+
L+
I/O Modules
230 V AC
CC/EU
–951
a)
c)
b)
Battery
L+
Power Supply
Load Power Supply 24V
Supply for the enable inputs from:
a) 6ES5 951-4LB11 load power supply
b) Battery
c) Terminals for 24 V on the front plate of the power supply
Configuring
Switching off the
CC
Separate or
Common
Shutdown of the
CC/EU and Load
Power Supply
Analog Input/Output Modules
Summary of Contents for S5-135U
Page 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Page 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Page 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Page 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Page 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Page 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...