3-10
System Manual
C79000-G8576-C199-06
À
Grounding strips
If there are no large-area metal-to-metal connections, you must
connect inactive metal parts such as cabinet doors and supports
with grounding strips. These should be short and have a large surface.
Á
Cabinet members
The cabinet members should have a large-area connection to the
cabinet housing (metal-to-metal connection).
Â
Mounting bracket for subrack
There must be a large-area metal-to-metal connection between
cabinet member and mounting bracket.
Ã
Signal lines
With shielded signal lines, the shield must be secured to the
protective conductor bar or an additionally fitted shield bar using
large-area cable clamps.
Ä
Cable clamp
The cable clamp must enclose and make contact with the shield braid
over a large area.
Å
Shield bar
This bar must have a large-area connection to the cabinet members
(metal-to-metal connection). It serves for grounding the cable shields.
Æ
Protective conductor bar
The protective conductor bar must have a large-area connection to
the cabinet members (metal-to-metal connection). The protective
conductor bar must be connected to the protective conductor system
via an external conductor (at least 10 mm
2
). This is essential for
providing a reliable path to ground for fault currents and interference
currents.
Ç
Conductor to the protective conductor system (ground point)
The conductor must have a large-area connection to the protective
conductor system (ground point).
Installation Guidelines
Summary of Contents for S5-135U
Page 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Page 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Page 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Page 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Page 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Page 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...