Wiring of Programmable Controllers for EMC
The following section describes:
Routing of cables within and outside cabinets
Equipotential bonding between devices
Single and double-ended connection of cable shields
Checklist for electromagnetically compatible installation
3.3.1
Routing of Cables
This section covers the routing of bus, signal and supply lines. The purpose
cable routing is to suppress crosstalk between cables laid in parallel.
For electromagnetically compatible routing of cables and lines, it is
expedient to subdivide the lines into the following line groups and lay the
groups separately.
Shielded bus and data lines (for programmer, OP, SINEC L1, SINEC L2,
printer, etc.)
Shielded analog lines
Unshielded lines for DC voltage
v
60 V
Unshielded lines for AC voltage
v
25 V
Coaxial cables for monitors
Unshielded lines for DC voltage > 60V and
v
400V
Unshielded lines for AC voltage > 25V and
v
400V
Unshielded lines for DC and AC voltage > 400V
Lines for SINEC H1
From the combination of individual groups in the following table, you can
read off the conditions for laying the line groups.
Group A
Group B
Group C
Group D
Group A
Group B
Group C
Group D
Routing of Cables
Within and
Outside Cabinets
Group A
Group B
Group C
Group D
Installation Guidelines
Summary of Contents for S5-135U
Page 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Page 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Page 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Page 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Page 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Page 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...