![Siemens S5-135U System Manual Download Page 248](http://html.mh-extra.com/html/siemens/s5-135u/s5-135u_system-manual_377341248.webp)
5-108
System Manual
C79000-G8576-C199-06
When the TTY submodule is delivered, the jumpers are set as shown in the
following figure. As a rule, therefore, you can use the TTY submodule
immediately.
Backplane Connector
J3
J4
J2
J1
1
2
3
Front Connector
25-Pin Sub. D-Type
1
2
3
Figure 5-21
TTY Submodule: Jumper Settings when Delivered
The polarity of the transmit and receive data is changed over with jumpers J1
and J2:
1
2
3
J1
Transmit data negated
Transmit data in normal polarity
J2
Receive data in normal polarity
Receive data negated
The 24 V source voltage for generation of the loop current can be allocated
with jumper J3:
1
2
3
J3
24 V will be applied from Pin 9 of
the sub. D connector
24 V will be applied from the
backplane connector (internally)
Jumper Settings
on the TTY
Submodule