Checklist for the Electromagnetically Compatible Installation of
Control Systems
EMC Measures
Notes
Connection of inactive parts
(Section 3.2)
Check, in particular, the connections on:
Subracks
Cabinet members
Shield and protective conductor bars
Do all inactive metal parts have a large-area, low-impedance
interconnection and ground?
Is there a satisfactory connection to the ground/protective conductor
system?
Have insulating layers on painted and anodized surfaces been
removed, or have special contact washers been used for the
connections?
Are connections protected from corrosion, e.g. by grease?
Are cabinet doors connected to the cabinet element with grounding
strips?
Routing of cables
(Section 3.3.1)
Cabling subdivided into line groups?
Supply cables (230 to 400 V) and signal lines laid in separate ducts or
bundles?
Equipotential bonding
(Section 3.3.2)
With a separate arrangement, check that the equipotential bonding
conductor has been correctly laid.
Shielding of cables
(Section 3.3.3)
Have metal connectors been used throughout?
Are all analog and data lines shielded?
Are line shields connected to the shield or protective conductor bar at
the cabinet entry?
Are line shields secured with cable clamps over a large area and at
low impedance?
Are line shields connected at both ends where possible?
Inductances
(Section 3.3.4)
Are contactor coils which are switched via contacts, fitted with
quenching elements?
Installation Guidelines
Summary of Contents for S5-135U
Page 10: ...x SystemManual C79000 G8576 C199 06 Contents ...
Page 18: ...1 8 SystemManual C79000 G8576 C199 06 Notes on Using this Manual and on the CE Symbol ...
Page 66: ...3 40 SystemManual C79000 G8576 C199 06 Installation Guidelines ...
Page 496: ...9 114 SystemManual C79000 G8576 C199 06 Analog Input Output Modules ...
Page 536: ...11 24 SystemManual C79000 G8576 C199 06 Connector Assignments ...
Page 558: ...Index 8 SystemManual C79000 G8576 C199 06 Index ...