7
Configuration
Configuring the Fire network
48
Building Technologies
A6V10854379_a_en
CPS Fire Safety
25.01.2019
9.6
Configuring the Fire network
This configuration task is carried out in Composer.
The communication between FS20/FS720 and the NK8237 IEC Gateway is based
on BACnet/IP. The following rules apply:
⚫
The FS20/FS720 and NK8237 units must share the same BACnet Virtual
Network (typically =1).
⚫
If the FS20/FS720 and NK8237 units do not share the same IP subnet,
appropriate IP and BBMD settings must be configured.
⚫
BACnet Device Identifiers must be uniquely defined for each unit including
NK8237.
Note: NK8237 supports only BACnet IDs in the range 1 through 65533.
⚫
The Device Identifier set for NK8237 must match the client ID expected by
FS20/FS720 configuration.
9.6.1
FS20 fire system
Configuration Procedure
1. Select the main node of the project.
2. In the left-hand bar, click the Generic Template icon .
A new node is added to the project structure.
3. Select the new folder and enter its name in the Description field of the Node
tab.
Adding the FS20 fire system node
1. Select the new folder.
2. In the left-hand bar, select the Fire Folder icon .
3. In the menu that appears, select the FS20 icon to add a new fire system
node.
A new node is added to the project structure.
Importing the FS20/FS720 configuration metafile (SiB-X)
1. Select the FS20 node.
2. In the Composer menu, select Tools > Import to start the import.
The software presents a browse window to search for the file to import (a
SiB-X file with extension XML is expected).
3. Using standard Windows controls, do the following:
–
Locate the XML file.
–
Select it and click Open.
A new window appears and displays the list of the stations included in the
system and represented in the SiB-X file.