Page 64
Milltronics SF 500 - INSTRUCTION MANUAL
7ML19985CN01
mmm
mm
PI
D Co
ntr
ol
Local: the setpoint is the value entered into P415.
mA Input 1: the setpoint is the mA value on input 1, terminals 5 and 6 on the mA I/O board.
mA Input 2: the setpoint is the mA value on input 2, terminals 7 and 8 on the mA I/O board.
P250-01 mA Input Range
E
Select 1- 0 to 20, 2-4 to 20
2
P255-01 mA Input Function
E
Select: 0, 1-PID SP, 2-PID PV
0
P401-01 PID Update Time
E
Readings between PID Updates
1
P402 Process Variable Source
E
1-Rate, 2-mA In1, 3-mA In 2
P405-01 Proportional Term
E
Enter
0.40
P406-01 Integral Term
E
Enter
0.2
P407-01 Derivative Term
E
Enter
0.05
P408-01 Feed Forward Term
E
Enter
0.3
P410-01 Manual Mode Output
E
Current Output Value
0
P414-01 Setpoint Configuration
E
0-Local, 1mA In 1, 2-mA In 2
0
P415-01 Local Setpoint Value
E
Enter Setpoint
0
Select the appropriate range for the mA
input signal
Assign either:
1, PID setpoint, or
2, process variable as the
function of the mA input
% value of output during manual
operation, P400 = 1
Enter the value for the feed forward
term, e.g. nominal value of 0.3
Selection of setpoint source:
0 = local (keypad or Dolphin Plus)
1 or 2 = mA input
Enter the value for the derivative term,
e.g. nominal value of 0.05
Select the source. Rate is an internal
values.
Enter the value for the integral term,
e.g. nominal value of 0.2
Enter the value for the proportional
term, e.g. nominal value of 0.4
Enter the value, e.g. nominal value of 1
Enter the setpoint value in engineering
units.
Not applicable if P414 = 1 or 2