
7ML19985CN01
Milltronics SF 500 - INSTRUCTION MANUAL
Page 111
mm
mmm
Pa
ra
m
ete
rs
Example:
Setpoint = 1000
Manual Pre-Act = 20
The gate shuts off at 980. The batch value of 1000 is met as feeding system empties.
P598 Span Adjust Percentage
Accessible only through manual span adjust (P019), when percent change (1) is selected.
Refer to
% Change
on page 30.
Totalization (P619 - P648)
The following parameters are specific to the use to the SF 500 totalizers. Refer also to
Operation / Totalization
P619 Totalling Dropout
This parameter sets the limit, in percent of design rate, below which material rates are
not totalized. (
f
= 3.0)
The value of 0 is reserved to allow both negative and positive totalization.
Enter drop out value in % of design rate.
P631 Totalizer Resolution
This parameter sets the resolution of the totalizer selected.
Totalizers are:
-01, totalizer 1
-02, totalizer 2
-03, verification totalizer
-04, material test totalizer
-05, batch totalizer
Entry:
1 = 0.001 (one thousandth)
2 = 0.01 (one hundredth)
3 = 0.1 (one tenth)
4 = 1 (unit)
f
5 = 10 (x ten)
6 = 100 (x hundred)
7 = 1000 (x thousand)