Milltronics SF 500 – INSTRUCTION MANUAL
Page 19
mmm
mm
M
odes of Op
ear
ati
on
display is programmed (P081) to scroll through rate, and totalization (P647), either
automatically, or by pressing the enter key.
If the SF 500 is programmed for batch control, the batch display is added to the display
scroll. Refer to
Batch Control (P560 - P568
Batching
Access PROGRAM mode, zero and span calibration from RUN Mode.
PROGRAM mode allows viewing, and with security permission (P000), editing parameter
values. While in PROGRAM mode, RUN mode functions are still active, i.e.: rate, relay, mA
output and totalization. If PROGRAM mode is left idle for a period of ten minutes, the SF
500 automatically reverts to RUN mode.
Zero and span calibrations effectively halt RUN mode while they are in progress. During
this time, totalization ceases, and all mA outputs, except for PID, fall to zero.
Rate
becomes
Rate
Total 1
Total 2
Key
PROGRAM Mode
RUN Mode
1
2
3
4 (EDIT Mode), Scroll Up (VIEW
Mode)
Scroll Up through PID Local Set-
point and Manual Output Values
5
6
7
8 (EDIT Mode), Scroll Down
(VIEW Mode
Scroll Down through PID Local
Setpoint and Manual Output Val-
ues
9
0
Decimal Place
- (Dash)
Toggle between PID auto/manual
Enter RUN Mode
Enter PROGRAM Mode
Press either the ZERO key or the
SPAN key to initiate Calibration
Press either the ZERO key or the
SPAN key to initiate Calibration