Milltronics SF 500 – INSTRUCTION MANUAL
7ML19985CN01
mmmm
m
Recalibr
at
ion
Access
Press
Access
Press
Access
Press
Calibrate the mA inputs on the SF 500 to the 4 and 20 mA levels of the weigh bin. 4 mA is
calibrated with the weigh bin empty, using P261-01 or –02. 20 mA is calibrated with the
weigh bin full, using P262-01 and P262-02.
P357-01 On-line Calibration Limits
V
MAX Limit:
90.0
P357-02 On-line Calibration Limits
V
HIGH Limit:
70.0
P357-03 On-line Calibration Limits
V
LOW Limit:
30.0
limit as a percentage