7ML19985CN01
Milltronics SF 500 - INSTRUCTION MANUAL
Page 103
mm
mmm
Pa
ra
m
ete
rs
P350 Calibration Security
Provides additional security to the global lock (P000).
On-line Calibration Options (P355 to P358)
P355 On-line Calibration Feature
Enables On-line Calibration.
Entry:
0 = OFF
f
1 = ON
P356 On-line Calibration Reference Weight
Enter the weigh bin reference weight, (in units selected in P005), range 0.000 to 99999.
(
f
= 0.000)
P357 On-line Calibration Limits
Used to enter the weigh bin limit settings.
P357.1
MAX LIMIT, range 0.0 to 100.0 (
f
= 0%)
P357.2
HIGH LIMIT, range 0.0 to 100.0 (
f
= 0%)
P357.3
LOW LIMIT, range 0.0 to 100.0 (
f
= 0%)
zero
span
Reset
T1
entry:
0 = no additional security.
f
Yes
Yes
Yes
1 = in addition to P000 lock; no span.
Yes
No
Yes
2 = in addition to P000; no zero, no span.
No
No
Yes
3 = in addition to P000; no zero, no span,
no totalizer 1 (T1) reset.
No
No
No
Note:
If SW1 is set to the left position, it will only allow the Zero function.
Note:
On-line calibration options must be enabled (P355 = 1) before they
become available.