Mounting/Installation
Installing the radio smoke detector DOW1171
5
51 | 82
Building Technologies
009865_m_en_--
Fire Safety
2015-11-06
Inserting the batteries
WARNING
Short-circuit as a result of incorrectly inserting batteries
Warming of batteries and risk of fire
●
When inserting battery, note polarity.
Insert the batteries in the devices just before commissioning the fire detection
installation.
w
The radio smoke detector DOW1171 is installed on the base DBW1171.
1. Remove the radio smoke detector DOW1171 from the radio base DBW1171.
2.
WARNING! Device does not work! Only use the battery type intended for
the device!
3. Connect clip to 9 V lithium manganese dioxide battery contacts and insert
battery in back box's battery compartment.
– Repeat this step for the second battery.
4. Install the radio smoke detector in the base.
a
The radio smoke detector is ready for commissioning.
Battery compartment and log-on button on the DOW1171
1 Battery compartment for two 9 V
lithium manganese dioxide
batteries
2 'New' log-on button
2