Structure and function
Function
3
36 | 82
Building Technologies
009865_m_en_--
Fire Safety
2015-11-06
3.10.1 Radio gateway FDCW221 diagnosis levels
The radio gateway monitors its operation largely autonomously.
The following diagnosis levels are derived from the different control measurements:
●
Normal
●
Replacement recommended
●
Replacement necessary
●
Fault
For details, see table below.
When a fatal error occurs, which impairs the function of the radio gateway, a fault
message is reported and displayed on the control panel.
To remedy the cause, additional information is available in the radio gateway. This
can be displayed by the detector exchanger and tester FDUD292 or the intelligent
detector tester FDUD293 (as of software V2.1) for example.
You will find more information in documents 007227 and 009718.
Display on the test device
Meaning
Measures
'no deviation'
Normal, no fault is present
Radio gateway is fully functional
None
'advice excha.'
1
Replacement recommended
Radio gateway is still functional in spite of the battery
voltage being too low:
●
FDCW221
Replace battery
'needed excha.'
1
Replacement necessary
Radio gateway is only being supplied with power via
the detector line:
●
FDCW221
Replace or insert battery
Any fault message
Fault present
Alarming no longer guaranteed:
●
FDCW221
●
Configure radio cell
●
Replace radio gateway
Supply error
●
Check detector line voltage
●
Replace radio gateway
Software error (Watchdog error)
Replace radio gateway
Memory error
Replace radio gateway
Communication error between radio gateway and
control panel
Remedy cause
1
The information displayed on the detector exchanger and tester is always in
English; no translation into the corresponding language.
The status 'Any fault message' can be displayed together with another status, e.g.
'needed excha.' (replacement necessary).