Mounting/Installation
Installing the radio smoke detector DOW1171
5
50 | 82
Building Technologies
009865_m_en_--
Fire Safety
2015-11-06
5.2 Installing the radio smoke detector DOW1171
w
Ensure that the radio smoke detector DOW1171 is connected to the radio
gateway FDCW221 from its intended location.
1. Define the mounting location of the base such that the alarm indicator of the
radio smoke detector DOW1171 is clearly visible from the investigation route.
2. Install the base with two screws on a level surface.
– Note the minimum distances to be complied with.
3. Install a designation plate DBZ1193A (accessory) if necessary.
4. Install the radio smoke detector DOW1171 on the base DBW1171.
Mounting location of the radio smoke detector
1 DOW1171 radio smoke detector
3 Investigation route
2 Alarm indicator
Base DBW1171 with designation plate DBZ1193A
2
3
500 mm
20 mm