4 - 101
RCM-1 Connections and Ratings
NOTES
1. Use 18 AWG
minimum wire.
2. Limit the maximum
resistance of loop
total from the first
RCM to the last RCM
to 100 ohms.
Maximum line
capacitance = 1µF.
3. The wiring is power
limited to NFPA 70
per NEC 760.
4. Maximum voltage is
1.5V RMS.
5. Maximum current is
50mA.
6. Refer to wiring
configurations for
the OCC and ACM on
proper EOLR
placement.
Style 4 Repeater Connection
The RCM-1 can be used as a repeater
when the required global riser exceeds
100 ohms. Do not install more than
two repeaters in any global riser.
Riser Repeater Wiring
(See Note 6)
S2 SETTINGS
SW
Description
Location
B
Location
B
1
1
Copper config
off
off
2
Copper config
on
on
3
Copper config
on
on
4
Copper repeater
on
off
5
Fiber config
on
on
6
Fiber config
on
on
7
Style 7
on
on
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...