E - 2
Appendix E
With Device Confirmation, the B
ð
C
verification time known as System
Justified Alarm time is also adjustable.
It is the same time used by both
ionization and photo detectors. If a
device is individually selected for alarm
verification, the alarm verification
feature takes priority over the device
confirmation option. For adjustment
ranges, refer to the
CSG-M Program-
ming Manual
, P/N 315-090381.
There is an Override menu selection in
the Test menu of revision level 3.00 or
higher of MXL. Select
Alr_Verify
to
disable all alarm verification or select
Alr_Confirm
to disable all alarm confir-
mation for a period of up to 4 hours or
until manually re-enabled.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...