3-46
Operation
The System displays the following four
sensitivity settings for XLD-1 devices:
Hi 2 Hi 1 Norm Lo 1
or
The System displays the following
seven sensitivity settings for ALD-2I
devices:
Hi 3 Hi 2 Hi 1 Norm Lo 1 Lo 2 Lo 3
Select the level you wish to set for the
smoke detector specified and press
ENTER.
The System makes the change
in the sensitivity setting.
Press
NEXT
to move through the
devices until you display the ones you
want to change. Follow the instruc-
tions above for making the changes.
When the System has displayed the
highest numbered device for the
module specified, it returns to the
Control menu. To change the sensitiv-
ity settings at another module address,
select
Senstvty
and follow the previ-
ous instructions.
If you attempt to change the sensitivity
setting of another type of device, the
System displays:
Not a Smoke Detector
If you enter any address for which
there is no device assigned, the System
displays:
No Device Assigned
To leave the Sensitivity menu without
going through the entire list, press the
Up arrow key. The System displays the
Control
menu.
Control: Arm/dis
Use Control Arm/dis to enable or
disable the operation of an initiating
device.
Select
Arm/dis.
The System asks you
for the module number and device
number of the device you wish to arm
or disarm:
Type In Module & Device: -
Type the three-digit module number
and three-digit device number using the
numeric keypad and press
ENTER
.
The System offers you a choice of
arming or disarming the device:
Arm Disarm
Highlight your choice and press
ENTER.
The System makes the change. When
you disarm an input device, the System
automatically annunciates the disarming
as a
Trouble
and lights the PARTIAL
SYSTEM DISABLE LED.
Press
NEXT
to move through the
devices until you display the ones you
want to change. Follow the previous
instructions for making the changes.
When the System has displayed the
highest numbered device for the
module specified, it returns to the
Control menu. To arm or disarm an-
other module device, select
Arm/dis
and follow the previous instructions.
Control: Output_on/off
Use Control Output_on/off to arm or
disarm the operation of an output
device. In addition, you can energize
(turn on) or de-energize (turn off)
disarmed output devices.
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...