3-37
Operation
each loop. XLD-1 modules have
four
sequential module numbersone
number for each analog loop.
List: Voltages - Analog
The display for Analog voltage is
similar to the following (readings are
dynamic):
001-001 ANALOG2 = 2.75 VOLTS
List: Voltages - Thresh
The display for Threshold voltage is
similar to the following:
001-001 THRESHOLD = 4.75 VOLTS
List: Voltages - Sens
The display for Sensitivity voltage is
similar to the following (readings are
dynamic):
001-001 SENSTVTY = 2.00 VOLTS
NOTE:
Only XLD-1 modules will have
the following additional List Voltage
menu items (These menu items will
not
appear for ALD-2I modules):
List: Voltages - Calib
The display for XLD-1 calibration
voltage is similar to the following
(readings are dynamic):
003-001 CALIBRATION = 4.00 VOLTS
List: Voltages - ID
The display for XLD-1 ID voltage is
similar to the following (readings are
dynamic):
003-001 ID = 2.00 VOLTS
List: Voltages - ID2
The display for XLD-1 ID2 voltage is
similar to the following (readings are
dynamic):
003-001 ID2 = 0.00 VOLTS
If a binary data reading (in hexadeci-
mal) is wanted for any of the above
voltages,
press the 0 key on the
numeric keypad to toggle the display
between the VOLTS response and the
HEX response. An example of the HEX
display is:
003-001 ANALOG2 = 16 HEX
NOTE:
When you ask for any voltage,
the System displays
Please wait for
response
until it receives a reading
from the device; if you have just reset
the System, it alternates the above
message with the message
Device
being initialized.
If the module number entered is not
an analog loop,
the System displays:
Not Analog Loop
If the device address has no device
assigned by CSG-M,
the System
displays:
No Device Assigned
When displaying sensitivities, if the
device is not a smoke detector,
the
System displays:
Not a Smoke Detector
To print the voltages of all devices
assigned to a specified module,
press
when the
V
in
Voltages
is blinking. The System
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...