4 - 50
MOI-7, MOD-16, MID-16 Connections and Ratings
NOTES
1. 18 AWG minimum for
all input connections.
2. 14 AWG minimum for
supply connections
(TB1-9 and 10, TB2-9
and 10).
3. All wiring must be
in accordance with
NEC 760.
4. All wiring must
conform to local codes
and to the authority
having jurisdiction over
the installation.
5. All wiring to MID-16,
MOD-16, or MOI-7
(non-network) modules
is unsupervised. Any
wiring leaving the
enclosure must be
within 20 feet, in rigid
conduit, and must not
leave the room.
6. For additional
information see
MOI-7 Installation
Instructions,
P/N 315-092799
7. A maximum of 8
MID-16s can be used
with the MOI-7.
8. P1 is connected in
parallel with TB1.
9. P2 is connected in
parallel with TB2.
MID-16
Electrical ratings:
Module power
5VDC
2mA max
Input ratings:
Input voltage range
18-31 VDC
Input impedance
8K ohms
Input current
2mA max
MID-16 Wiring
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...