3-44
Operation
To print the analog loops current
readings in percent/ft obscuration,
press
when the
P
in
Percent/ft
is blinking. The System asks you for a
module number.
Type In Module Number:
Type the three-digit module number
using the numeric keypad and press
ENTER.
The System shows the
following menu for that device (the
S
in
Senstvty
will be blinking):
001-001 Senstvty Pre-alarm Analog
The System prints either the Sensitiv-
ity, Pre-alarm, or Analog readings of all
the devices for the specified module in
a format similar to the following (ND =
No Device):
%/ft sensitivities for module 1
1-3.00 2-NA
3-1.4
4-3.1 ...
11-ND
12-ND
13-ND
14-ND
...
21-ND
22-ND
23-ND
24-ND
...
31-ND
32-ND
33-ND
34-ND
...
41-ND
42-ND
43-ND
44-ND
...
51-ND
52-ND
53-ND
54-ND
...
List: ASD_apps
Use List ASD_apps to display operational
characteristics of the ASD devices.
To display the operational charac-
teristics of one device,
press
ENTER
to select
ASD_apps.
The System asks
you for a module and device number:
Type In Module & Device: -
Type the three-digit module number
and three-digit device number using
the numeric keypad and press
ENTER
.
The System displays the currently
assigned application for the device
specified. (Refer to the chart in
dix I- Application Specific Detection
Press
NEXT
to display the address and
assigned application of each succeed-
ing device. The System will exit the
ASD_Apps menu if there are no more
ASD devices in that module.
To print the operational characteris-
tics of the ASD devices assigned to
an ALD Loop,
press
when the
A
in
ASD_Apps
is blinking. The Sys-
tem asks you for a module number:
Type In Module Number:
Type the three-digit module number
using the numeric keypad and press
ENTER.
The System prints a list of all
the applications currently assigned to
all the ASD devices in that ALD loop in
a format similar to the following (ND =
No Device):
ASD Applications for module 1
1-NONE 2-PARK 3-ND
4-OFFC ...
11-ND
12-ND
13-ND
14-ND
...
21-ND
22-ND
23-ND
24-ND
...
31-ND
32-ND
33-ND
34-ND
...
41-ND
42-ND
43-ND
44-ND
...
51-ND
52-ND
53-ND
54-ND
...
List: Disarmed_state
Use List Disarmed_state to show the
alarm state of a currently disarmed
device.
To display the alarm state of one
module,
press
ENTER
to select
Disarmed_state.
The System displays
the following:
In Stat Out Stat
Choose either
Input Status
or
Output
Status.
The System then asks you for
a module number:
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...