1-4
Description
X = Not Required
*
One CSM-4 circuit must be configured for alarm
transmission. In addition, depending on the local
authority having jurisdiction, additional circuits may
be required for Supervisory or Trouble transmission.
** Any one of these modules is sufficient as an
initiating device.
*** Only TRI-60, TRI-60R, TRI-60D, TRI-B6, TRI-B6R, and
TRI-B6D can be used as security devices.
**** Do not use NET-4s and NET-7s in the same system.
NOTES
a. See Silent Knight Model 5128/5129 Connections and
Ratings for NFPA 72 Central Station.
b. Refer to System MXL Wiring Diagram, P/N 575-095370
c. The MMB must be programmed by CSG-M for all
System configurations (See
CSG-M Programming
Manual
, P/N 315-090381).
d. UL 1076 requires a Model TSW-2 tamper switch and a
TSP-40 printer.
e. The batteries available are: BP-61, BTX-1, and BTX-2.
The BP-61 is a module consisting of four 6V, 15 AH
batteries. The BTX-1 batteries are a pair of 12V, 31 AH
batteries. The BTX-2 batteries are a pair of 12V, 55 AH
batteries. Actual battery size depends on System
configuration.
f. See Appendix C for Battery Calculations.
g. The PSR-1 is not listed for security.
h. The PIM-1 requires the connection of the RC-119
supervised printer. The TSP-40 is not required.
j. The CMI-300 is not listed for UL 1076 application.
k. Refer to the CSM-4 Installation Instructions (P/N
315-090854) for programming.
l. The MXL System is FM approved for proprietary
fire for Fire Alarms, Water Flow, Sprinkler
Supervisory Service and Intrinsically Safe Operation.
Minimum MXL Configuration To Meet NFPA 72, UL 1076, and NFPA 12A, 13, and 2001
MINIMUM MXL CONFIGURATION TO MEET NFPA 72, UL 1076, AND NFPA 12A, 13, AND 2001
Module
Description
NFPA Minimum Quantity
Local
Auxiliary
Remote
Station
Proprietary
Central
Station
a
UL 1076
b
12A, 13, or
2001
l
MMB-1/-2
c
MXL Main Unit
1
1
1
1
1
1
1
MPS-6
Power Supply
1
1
1
1
1
1
1
MPS-12
Power Supply
1
1
1
1
1
1
1
MKB-2
Keyboard/Annunciator Panel
1
1
1
1
1
1
1
TSP-40
Logging Printer
X
X
X
1
X
1
d
X
MOM-4
Optional Module Card Cage
X
1
1
X
X
X
X
CSM-4
Signal Module
X
1
k
1 or 2*
k
X
X
X
1
k
CZM-4
Conventional Zone Module
**
**
**
**
**
X
**
ALD-2I
Analog Loop Driver
**
**
**
**
**
***
**
CZM-1B6
Remote Conventional Zone
Module
**
**
**
**
**
X
**
Batteries
e,f
1
e
1
e
1
e
1
e
1
1
1
e
TSW-2
Tamper Switch
X
X
X
X
X
1
d
X
PSR-1
Remote Power Supply
X
X
X
X
X
X
g
X
NET-4/-7
Communication Interface****
X
X
X
X
X
X
X
MOI-1/-7
Voice and Annunciator Driver
X
X
X
X
X
X
X
MOD-16
Output Driver
X
X
X
X
X
X
X
MID-16
Inpout Module
X
X
X
X
X
X
X
PIM-1
Peripheral Interface Module
X
X
X
1
h
X
1
h
X
CMI-300
MXL/CXL Interface
X
X
X
X
X
X
j
X
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...