ZCT-8B Connections and Ratings
ALL ZONES SUPERVISED, POWER LIMITED
All wiring must be in accordance with Article 760 of
NEC or the local building codes.
Maximum Loop Resistance: 10 ohms
Minimum Wire Size: 18 AWG
Maximum Wire Size: 14 AWG
Supervised Telephone Zone Connections
Supervised:
9 VDC, 9mA max
Active:
12.5 VDC, 300mA max
Connect shield to negative zone terminal
ZCT-8B Telephone Zone Wiring Diagram