Connectivity and communication with 'Station'
Initializing 'Station'
9
79 | 118
Building Technologies
A6V10211100_f_en_--
Fire Safety
2015-12-15
Initialize 'Station'
NOTICE
Connection module (card cage) FCA2006-A1 defective or installed incorrectly
Control panels identified incorrectly, e.g. FC726 identified as FC724.
● Check that the connection module (card cage) FCA2006-A1 is installed
correctly.
NOTICE
Faulty initialization for networked station
During initialization, the station must not be connected to the network or any other
station.
ϖ
The PC is connected locally to the ↑ 'Station'.
1. Highlight the 'Station' you want to initialize.
2. Select the 'Commissioning' > 'Initialize station' menu item.
The following window is opened:
3. Click on 'Start'.
The 'Set the station to access level 3' window opens.
4. Press <MENU> on the 'Station' and enter a valid PIN.
5. Click on 'OK' in the 'Set access level' window.
The 'Station' is initialized.
The 'Station' is restarted.
After a few minutes, the 'Buzzer' sounds twice.
6. Press <Acknowledge> on the ↑ Person Machine Interface to switch off the
'Buzzer'. Do not perform any more actions on the 'Station' until the 'Buzzer' has
sounded for the second time.