Mounting
Mounting instructions
5
24 | 118
Building Technologies
A6V10211100_f_en_--
Fire Safety
2015-12-15
5.2.1 Surface-mounted assembly
● Any surface irregularities can be compensated with washers or wooden
wedges.
● The rear panel is attached to the wall using screws with a diameter of 6 mm.
● The supplied edge protection strip must be placed around rectangular breakout
openings.
● Depending on the cable type, up to 8 cables can be fed through each round
opening (20 mm with rubber grommet).
● Only one cable may be fed through each screwed cable gland (not within the
scope of delivery).
Mounting steps
1. Break out the required cable openings on the rear panel.
Signal and control cables must be fed into the housing from above or from the
rear (EMC protection).
2. Screw in the cable gland for the power cable (Ø 20 mm), or insert a rubber
grommet.
3. Mark the bore holes for the dowels using the supplied drilling template. The
cardboard cover in the packaging is also the drilling template. The holes in the
cardboard cover correspond to the mounting holes in the rear panel.
The holes can also be marked using the information in the product insert.
4. Drill the holes and insert the supplied dowels.
5. Attach the housing using the supplied screws.
6. Stick the supplied aluminium stickers over all holes for wall mounting.
7. Feed the mains cable into the housing and fix the cable with cable ties.
8. Protect the electronics if necessary using the cover of the packaging or other
suitable means.
9. Regarding the mounting location of the FC721, please adhere to the
instructions in this chapter.