Installation
Power supply - mains voltage connection
6
51 | 118
Building Technologies
A6V10211100_f_en_--
Fire Safety
2015-12-15
Determining the battery type
Determine the battery type on the basis of the calculated battery capacity (see
table).
Designation
Type
Capacitance Order number
Battery (12 V, 7 Ah, VDS)
FA2003-A1
7 Ah
A5Q00019353
Battery (12 V, 12 Ah, VDS)
FA2004-A1
12 Ah
A5Q00019354
Battery (12 V, 17 Ah, VDS)
FA2005-A1
17 Ah
A5Q00019677
Battery (12 V, 26 Ah, VDS)
FA2006-A1
26 Ah
A5Q00019356
Table 2: Permitted batteries
NOTICE
Hardware damage
● Due to CE conformity only UL94-V2 batteries may be used.
Notes
● To achieve the system voltage of 24 V, two batteries must always be
connected in series.
● Batteries are not included in the scope of supply of the stations and must be
ordered separately.
● The battery capacity determines the charging current. The charging current
must be taken into account when calculating the power supply.
● The dimensions of the batteries are needed to determine the housing type.
Restriction of the battery dimensions
● With greater battery capacities, the additional empty housing (Standard) should
be used with a 150 W power supply.