Install internal components
Alarm control panel PT2005-A1
6
94 | 173
A6V10430579_en--_b
6.13 Alarm control panel PT2005-A1
The 'Alarm control panel (19")' PT2005-A1 is designed to be mounted in a 19''
cabinet.
6.13.1 Installation
The PT2005-A1 provides 7 colored single wires to connect DC 10 V and inputs and
output signals to a digital audio matrix.
6.13.2 Connect inputs and outputs
The PT2005-A1 provides inputs to connect the LEDs and outputs to connect the
buttons.
Input and output wiring
Wire
Color
Description
Connect to matrix
1
Red
Power input 10 V
10 V output
2
Purple
Button Voice alarm 'Initiate / Auslösen' Logic input
3
Brown
LED Voice alarm 'Initiate / Auslösen'
Logic output
4
White
Button Voice alarm 'Reset /
Rückstellen'
Logic input
5
Yellow
Button Voice alarm 'Silence /Stumm'
Logic input
6
Green
LED Voice alarm 'Silence /Stumm'
Logic output
7
Gray
Button 'Fault Indication Reset /
Quittierung Störung'
Logic input
Table 53: PT2005-A1 input and output wiring