Install internal components
Use control inputs and outputs
6
70 | 173
A6V10430579_en--_b
6.4.4 Use logic control outputs
The connected components can be powered with the internal 10 V with the
connected component connected to a logic output.
Fig. 46: Wiring diagram for open collector logic control outputs with 10 V
If the connected components require a different voltage, these components can be
powered with an external power source. The negative output of the external power
source must be connected to the GND of the system; the positive output is
connected to the component.
Fig. 47: Wiring diagram for open collector logic control outputs with external power
A recovery diode is required when a relay is connected to the logic output.
Fig. 48: Wiring diagram for open collector logic control outputs connecting relays