Install internal components
System operating unit (19'') PT2010-A1
6
A6V10430579_en--_b
91 | 173
6.11.5 Logic control outputs
The PT2010-A1 provides 4 logic control outputs on the connector 'X3'.
The logic control outputs are used to activate LEDs or communicate a status
change of the system.
The logic control outputs are open collector outputs which switch to IO-GND. A
power source is required to use the outputs.
● Max. current per output is 200 mA.
● Max. current on internal 12 V power source is 250 mA.
Logic control outputs connector - 'X3'
Pin
Description
Remark
1
O1
-
2
O2
-
3
O3
-
4
O4
-
5
IO-GND
IO-GND not connected to GND
6
12 V
12 V reference voltage
Table 49: PT2010-A1 logic control outputs connector - 'X3'
For use of logic control outputs, see Use logic control outputs [
6.11.6 Logic control inputs
The PT2010-A1 provides 4 potential-free logic control inputs on the connector 'X4'.
The logic control inputs are used to get information and controls from the
connected components.
● Logic 0 with input voltage <3 V
● Logic 1 with input voltage >7 V
Logic control inputs connector - 'X4'
Pin
Description
Remark
1
I1
-
2
I2
-
3
I3
-
4
I4
-
5
GND
IO-GND not connected to GND
6
10 V
10 V reference voltage
Table 50: PT2010-A1 logic control inputs connector - 'X4'
For use of logic control inputs, see Use logic control inputs [