Preparatory work
Electrical supply lines
3
30 | 173
A6V10430579_en--_b
3.3 Electrical supply lines
General guidelines
1.
Read the safety instructions for electrical installations in Safety regulations for
the method of operation.
2.
Batteries must only be inserted and connected in the housing by authorized
specialist personnel.
● The connections for the transmission paths and fuses must be clearly marked.
● The mains supply line must be designed with at least 1.5 mm
2
per conductor.
● The fuse for each outer conductor must be above the rated current indicated on
the type plate.
● In order to avoid an unintentional shutdown, the mains supply line must not be
routed via a switch.