6.12.3 Connect inputs and outputs
The PT2004-A1 and PT2007-A1 provide one connector ('CN2) with inputs to
connect the LEDs and outputs to connect the buttons and the fault relay.
Input and output connector - 'CN2'
Pin
Description
Remark
Connect to matrix
1
Operate
LED 'Operating / Betrieb'
Logic output
2
Fault
LED 'Fault / Störung'
Logic output
3
Alarm
LED 'Voice alarm / Sprachalarm'
Logic output
4
Warning
Buzzer
Logic output
5
Ack
Button 'Buzzer reset/Test /
Quittierung/Test'
Logic input
6
GND
GND reference voltage
GND
7
Fault
Fault relay
Logic input
8
Fault
Fault relay
10 V output
Table 52: PT2004-A1 and PT2007-A1 input and output connector - 'CN2'