ClareOne Water Detector                                                               Installation Manual 

CLR-C1-WTR

 

 

                                                                                                 

 

 

 

 

CLR-C1-WTR  IM V3 05012020

 

 

 

 

INTRODUCTION 

The CLR-C1-WTR Water Detector is not a 

self-contained warning device.  

For proper operation, it must be used in  

conjunction with a Clare Controls alarm  

system.  It is designed so that the  

transmitter mounts on a wall or other flat  

vertical surface, and the remote probe is placed in the 

location where water leakage is most probable.   

 

Moisture forming a bridge between the two metallic 

contacts on a remote probe is all that is needed for the 

unit to signal an alarm condition.  The output on the CLR-

C1-WTR will remain in alarm state until the moisture 

bridge is broken.  As sensitive as the Water Detector is, it 

will not alarm due to high humidity or condensation. The 

Water Detector is ideal for use in homes, offices, computer 

rooms, warehouses, etc. 

INSTALLATION 

When mounting the wireless device make sure  it is 

not mounted on metal or where there are any large 

metal objects between the device and the control 

panel, this can be tested prior to or after installation. 

 

Mounting the probe to a vertical surface like a wall 

enables you to monitor an area for rising water levels. 

Use where ever unwanted water may accumulate. 

Suggested areas near: water heater, washing 

machines, under sinks, and sump pumps 

 

Mount Transmitter using 

supplied double-sided tape. 

Probe mounts directly to the 

floor or can be attached to 

wall using tape or screws. 

MOUNTING:

 

Mount the transmitter as high as possible, the 

water Probe has a 6’ cable attaching it to the 

sensor.  The probe can be mounted to the wall 

or floor using mounting screws or adhesive 

strips provided. 

FEATURES 

·  Water Detection when liquid makes contact with probe.

 

·  Contacts above floor level to prevent false floor  

condensation detection. 

 ·  Checks for water constantly, requires two positive      

    checks for a valid alarm. 

·  Battery checked every hour.  

·  Batteries (2) CR2032. 

·  Tamper Switch: Included inside transmitter. 

PROGRAMMING 

1. Enter Programming Mode. 

2. Open and close the case to “tamper” the device. 

3. Customize name and settings as desired and 

touch “ADD”. 

TEST PROCEEDURES

 

To test the operational status, form a water bridge 

between the two metallic contact points with a moistened 

finger or cloth. If working properly, the detector will 

activate the warning device to which it is connected 

within approximately three seconds. The detector will 

reset automatically when the probe dries and there is no 

longer a water bridge between the two metallic contact 

points.  

SPECIFICATIONS 

Power Requirement Batteries:    2 - CR2032 

Approximate Battery Life:            5 years 

Replace Batteries:  

             (2) Panasonic CRT2-32, 

  

 

 

             Energizer CR2032, or  

                                                    Duracell DL2032 

Code Outputs:    

             Tamper, Tamper Restore,    

                                                    Alarm, Alarm Restore, Low    

                                                    Battery 

Transmitter Frequency:               433.95 MHz 

Supervisory Keep-Alive Interval: Every 60 Minutes 

RF Peak Field Strength:  

Typical 36000 uV/M at 3 m 

Operating Temperature:  

32° to 122°F (-40° to 60° C) 

Maximum Cable Length: 

72” 

Packaging Weight: 

 

.158 lbs. 

Transmitter Dimensions: 

2.71” H x .95” W x .56” D 

Probe Dimensions: 

 

.7” W x 1.77” L  x .38” D 

Mounting Probe: 

 

Wall surfaces using    

                                                    mounting screws or tape pad.                                             

Case Material:   

 

ABS Plastic 

 
 

 

 

  

Cover Latch 

 

 

Tamper Switch 

 

Battery 