SD39EAM-1r4
Maintenance
September 2005
3-3
3.4 Troubleshooting
Errors are annunciated by:
•
The module’s status LEDs (see Table 3-1)
•
The
4-mation
configuration software - Error codes and messages; refer to
Diagnostic Error Codes
and Software Messages
(document number CG39-19) or
4-mation
’s help file.
The
4-mation
configuration software runs on an IBM-compatible PC or the APACS+ Rack-mounted
Industrial Server (RIS).
Module status LEDs are located on the EAM’s bezel. Note LED indications, then refer to Table 3-1 for
EAM status and
4-mation
to determine the course of action.
Interconnect I/O Cable pin assignments are listed in Table 2-3. These are provided for troubleshooting a
suspect cable.
As necessary, check field wiring and field-located devices.
The EAM, Termination Strip, and Marshalled Termination Assembly are not field serviceable, except for
the EAM power fuse replacement. A failed assembly should be returned to the factory for repair.
Table 3–1 LED Status Indications
LED
INDICATOR
LED
INDICATION
MODULE STATUS
USER ACTION
Solid Green
Module OK; Configured with no faults ---
Flashing Green/ Black Module Not Configured; No fault or
failure
Configure module
Flashing Red/Green
Fault Detected; One or more channel
specific errors, or a less severe board
level error
Replace module or
channel fuse
Flashing Red/Black (1
per second)
1. Low or defective I/O supply
2. Failure Detected; Board level
problem
affecting more than one channel
Replace module
Flashing Red/Black (5
per second)
IOBUS Communication Error
1. Check ACM
2. Replace module
OK
Solid Red
Module Fault, Severe
Replace module
Solid Green
Module in Control
---
ACTIVE
OFF
Redundant EAM in Standby Mode or
off-line configuration of module
---
Summary of Contents for APACS+
Page 16: ......
Page 26: ...Installation SD39EAM 1r4 2 10 September 2005 Figure 2 3 EAM Marshalled Termination Assembly ...
Page 27: ...SD39EAM 1r4 Installation September 2005 2 11 Figure 2 4 Marshalling Termination Panel ...
Page 40: ...Installation SD39EAM 1r4 2 24 September 2005 Figure 2 9 Sample Input and Output Connections ...
Page 41: ...SD39EAM 1r4 Installation September 2005 2 25 Figure 2 10 I O Cable End Preparation ...
Page 42: ......
Page 47: ...SD39EAM 1r4 Maintenance September 2005 3 5 Figure 3 1 Cover Plate Securing Screws ...
Page 48: ...Maintenance SD39EAM 1r4 3 6 September 2005 Figure 3 2 User Replaceable Fuse ...