Maintenance
SD39EAM-1r4
3-8
September 2005
3.6
EAM Termination Strip Removal/Replacement
3.6.1 Removal
Procedure
Refer to Figure 2-2 and the following removal procedure:
1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field
devices connected to the Termination Strip.
2. Remove the associated EAM from its slot in the MODULRAC. Place the EAM in a static shielded
bag for protection.
3. Disconnect signal cables from the Termination Strip.
IMPORTANT
All signal cables should be labeled for correct reconnection.
4. Loosen the Termination Strip’s captive mounting screws. Gently lift the bottom of the Board in an
arc until the board is free of its alignment pin located immediately above the "MOORE" logo. Pull
the top of the Termination Strip from the grooved backplane spacer and lift it from the MODULRAC.
3.6.2 Replacement
Procedure
Refer to Figure 2-2 and the following replacement procedure:
1. Refer to section 2.4 and install the replacement Termination Strip.
2. Reconnect the signal cables.
3. Install the EAM. See section 3.5.
3.7
EAM Marshalled Termination Assembly Removal/Replacement
3.7.1 Removal
Procedure
Refer to Figure 2-5 and the following removal procedure:
1. As necessary, take appropriate steps to shutdown the processes monitored or controlled by the field
devices connected to the Termination Assembly.
2. Remove the associated EAM from its slot in the MODULRAC. Place the EAM in a static shielded
bag for protection.
Summary of Contents for APACS+
Page 16: ......
Page 26: ...Installation SD39EAM 1r4 2 10 September 2005 Figure 2 3 EAM Marshalled Termination Assembly ...
Page 27: ...SD39EAM 1r4 Installation September 2005 2 11 Figure 2 4 Marshalling Termination Panel ...
Page 40: ...Installation SD39EAM 1r4 2 24 September 2005 Figure 2 9 Sample Input and Output Connections ...
Page 41: ...SD39EAM 1r4 Installation September 2005 2 25 Figure 2 10 I O Cable End Preparation ...
Page 42: ......
Page 47: ...SD39EAM 1r4 Maintenance September 2005 3 5 Figure 3 1 Cover Plate Securing Screws ...
Page 48: ...Maintenance SD39EAM 1r4 3 6 September 2005 Figure 3 2 User Replaceable Fuse ...