SD39EAM-1r4
Specifications
September 2005
6-3
CATEGORY
SPECIFICATION
DATA
Minimum Pulse Width
Module Discrete Input
Sourcing
Input Filter Delay
Input Wetting Current
5.6 mS
20 mA
Module Discrete Input
Sinking
Input Filter Delay
11 mS
Module Discrete Output
Maximum Output Current
On State Voltage Range
Off State Leakage Current
40 mA
14 to 24 Vdc
0.05 mA
6.3 Electrical
Classification
IMPORTANT
Before installing, applying power to, or servicing an EAM, see the
module’s nameplate for its electrical classification.
6.3.1 CSA Hazardous Locations Precautions
This section provides CSA hazardous location precautions that should be observed by the user when
installing or servicing the equipment described in this Instruction. These statements supplement those
given in the preceding section.
DANGER
Electrical shock hazard
Explosion hazard
Will cause death, serious injury or property damage
•
Remove power from all wires and terminals and verify that there
are no hazardous voltages before working on equipment.
•
In potentially hazardous atmosphere, remove power from
equipment before connecting or disconnecting power, signal, or
other circuit, or extracting/inserting module.
•
Observe all pertinent regulations regarding installation in
hazardous area.
•
Ensure all devices are rated for hazardous (classified) locations.
Summary of Contents for APACS+
Page 16: ......
Page 26: ...Installation SD39EAM 1r4 2 10 September 2005 Figure 2 3 EAM Marshalled Termination Assembly ...
Page 27: ...SD39EAM 1r4 Installation September 2005 2 11 Figure 2 4 Marshalling Termination Panel ...
Page 40: ...Installation SD39EAM 1r4 2 24 September 2005 Figure 2 9 Sample Input and Output Connections ...
Page 41: ...SD39EAM 1r4 Installation September 2005 2 25 Figure 2 10 I O Cable End Preparation ...
Page 42: ......
Page 47: ...SD39EAM 1r4 Maintenance September 2005 3 5 Figure 3 1 Cover Plate Securing Screws ...
Page 48: ...Maintenance SD39EAM 1r4 3 6 September 2005 Figure 3 2 User Replaceable Fuse ...