7SR18 Applications Guide
Unrestricted Page 60 of 63
©2018 Siemens Protection Devices Limited
9.3 Trip/Close Circuit Supervision (74T/CCS)
Binary Inputs (BI) may be used to monitor the integrity of the CB trip and close circuit wiring. A small current flows
through the BI and the circuit. This current operates the BI confirming the integrity of the auxiliary supply, CB coil,
auxiliary switch, C.B. secondary isolating contacts and associated wiring. If monitoring current flow ceases, the BI
drops off and if it is user programmed to operate one of the output relays, this can provide a remote alarm. In
addition, an LED on the relay can be programmed to operate. A user text label can be used to define the operated
LED e.g. “Trip CCT Fail”.
The relevant BI is mapped to 74TCS-n or 74CCS in the INPUT CONFIG>INPUT MATRIX menu. To avoid giving
spurious alarm messages while the circuit-breaker is operating the input is given a 0.4 s Drop-off Delay in the
INPUT CONFIG>BINARY INPUT CONFIG menu.
To provide an alarm output a normally open binary output is mapped to 74TCS-n or 74CCS-n.
9.3.1
Trip Circuit Supervision Connections
The following circuits are derived from UK ENA S15 standard schemes H5, H6 and H7.
For compliance with this standard:
Where more than one device is used to trip the CB then connections should be looped between the
tripping contacts. To ensure that all wiring is monitored the binary input must be at the end of the looped
wiring.
Resistors must be continuously rated and where possible should be of wire-wound construction.
Scheme 1 (Basic)
Figure 9.3.1-1 Trip Circuit Supervision Scheme 1 (H5)
Scheme 1 provides full Trip supervision with the circuit breaker Open or Closed.
Where a ‘Hand Reset’ Trip contact is used measures must be taken to inhibit alarm indications after a CB trip.
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...