![Siemens 7SR18 Solkor Manual Download Page 266](http://html.mh-extra.com/html/siemens/7sr18-solkor/7sr18-solkor_manual_383100266.webp)
Chapter 4 - 7SR181 Solkor · Data Communications Definitions
© 2016 Siemens Protection Devices Limited
Chapter 4 - Page 47 of 80
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
(unsol. resp)
22
7
32-Bit Delta Counter
Change Event (with Time)
22
8
16-Bit Delta Counter
Change Event (with Time)
23
0
Frozen Counter Event
(Variation 0 is used to
request default variation)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
23
1 (default -
see note 1)
32-Bit Frozen
Counter Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
23
2
16-Bit Frozen
Counter Event
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
17, 28 (index)
23
3
32-Bit Frozen Delta
Counter Event
23
4
16-Bit Frozen Delta
Counter Event
23
5
32-Bit Frozen Counter
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
23
6
32-Bit Frozen Counter
Event (with Time)
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
23
7
32-Bit Frozen Delta Counter
Event (with Time)
23
8
16-Bit Frozen Delta Counter
Event (with Time)
30
0
Analog Input
- Any Variation
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
30
1
32-Bit Analog Input
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
2 (default -
see note 1)
16-Bit Analog Input
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
3
32-Bit Analog Input
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
4
16-Bit Analog Input
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
5
short floating point
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
30
6
long floating point
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
31
0
Frozen Analog Input
- Any Variation
31
1
32-Bit Frozen Analog Input
31
2
16-Bit Frozen Analog Input
31
3
32-Bit Frozen Analog Input
(with Time of freeze)
31
4
16-Bit Frozen Analog Input
(with Time of freeze)
31
5
32-Bit Frozen Analog Input
(without Flag)
31
6
16-Bit Frozen Analog Input
(without Flag)
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...