7SR18 Applications Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page 13 of 63
Section 2: Protection Functions
2.1 Time delayed over-current (51/51G/51N)
The 51-n characteristic element provides a number of time/current operate characteristics. The element can be
defined as either an Inverse Definite Minimum Time Lag (IDMTL) or Definite Time Lag (DTL) characteristic. If an
IDMTL characteristic is required, then IEC, ANSI/IEEE and a number of manufacturer specific curves are
supported.
IDMTL characteristics are defined as “Inverse” because their tripping times are inversely proportional to the Fault
Current being measured. This makes them particularly suitable to grading studies where it is important that only
the Relay(s) closest to the fault operate. Discrimination can be achieved with minimised operating times.
To optimise the grading capability of the relay additional time multiplier, ‘Follower DTL’ (Figure 2.1-1) or ‘Minimum
Operate Time’ (Figure 2.1-2) settings can be applied.
0.01
0.10
1.00
10.00
100.00
1000.00
1
10
100
1000
Current (x Is)
O
p
e
ra
ti
n
g
T
im
e
(S
e
c
o
n
d
s
)
0.01
0.10
1.00
10.00
100.00
1000.00
1
10
100
1000
Current (x Is)
O
p
e
ra
tin
g
T
im
e
(S
e
c
o
n
d
s
)
Figure 2.1-1 IEC NI Curve with Time Multiplier and Follower DTL Applied
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...