7SR18 Installation Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page
21 of
6.2 Protection Signalling Communication Connection
The connections between Local and Remote relays must be connected in a cross-over manner e.g. Tx
on Local relay to RX on Remote relay, or top connection on Local relay to bottom connection on
Remote relay.
6.3
Additional (Optional) Ethernet Connection for IEC 61850
Rear Ethernet Comms port Ch 1 and Ch 2 comprises
Duplex LC 100BaseF in acc. With IEEE802.3
Fibre–
Optic or
RJ45 100BaseF in acc. With IEEE802.3
electrical connectors.
When installing fibre, ensure that the fibres’ bend radii comply with the recommended minimum for the fibre used-
typically 50 mm is acceptable,
62.5/125
µ
m glass fibre with Duplex-LC connector
recommended for all
distances.
To
Control
System
Switch
Ch n
Ch 2
Ch 1
62.5/125
µm
fibre optic
with Duplex LC
connectors or RJ45
electrical connectors
Ch 2
Ch 1
Ch 1
Ch 3
Ch 2
Ch 1
Input
Ch 2
Figure 6.3-1 Ethernet connection for IEC 61850 (star connection)
Figure 6.3-2 Ethernet connection for IEC 61850 (ring connection)
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...