7SR18 Solkor Settings Guide
Unrestricted
Page 18 of 44
© 2016 Siemens Protection Devices Limited
Description
Range
Default
Gn 49 Capacity Alarm
Disabled, Enabled
Disabled
Gn 49 Capacity Alarm Setting
50, 51 ... 99, 100
50%
16 LINE CHECK
Description
Range
Default
Gn 50 LC Measurement
RMS, Fundamental
RMS
Gn 50G LC Measurement
RMS, Fundamental
RMS
16.1 50 LC-1
Description
Range
Default
Gn 50 LC-1 Element
Disabled, Enabled
Disabled
Gn 50 LC-1 Setting
0.05, 0.06 ... 49.5, 50
1xIn
Gn 50 LC-1 Delay
0, 0.01 ... 14300, 14400
0s
Gn 50 LC-1 Inrush Action
Off, Inhibit
Off
16.2 50 LC-2
Description
Range
Default
Gn 50 LC-2 Element
Disabled, Enabled
Disabled
Gn 50 LC-2 Setting
0.05, 0.06 ... 49.5, 50
1xIn
Gn 50 LC-2 Delay
0, 0.01 ... 14300, 14400
0s
Gn 50 LC-2 Inrush Action
Off, Inhibit
Off
16.3 50G LC-1
Description
Range
Default
Gn 50G LC-1 Element
Disabled, Enabled
Disabled
Gn 50G LC-1 Setting
0.05, 0.06 ... 49.5, 50
0.5xIn
Gn 50G LC-1 Delay
0, 0.01 ... 14300, 14400
0s
Gn 50G LC-1 Inrush Action
Off, Inhibit
Off
16.4 50G LC-2
Description
Range
Default
Gn 50G LC-2 Element
Disabled, Enabled
Disabled
Gn 50G LC-2 Setting
0.05, 0.06 ... 49.5, 50
0.5xIn
Gn 50G LC-2 Delay
0, 0.01 ... 14300, 14400
0s
Gn 50G LC-2 Inrush Action
Off, Inhibit
Off
17 SUPERVISION
17.1 CB FAIL
Description
Range
Default
Gn 50BF Element
Disabled, Enabled
Disabled
Gn 50BF Setting
0.05, 0.055 ... 1.995, 2
0.2xIn
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...