7SR18 Performance Specification
Unrestricted Page 36 of 44
©2018 Siemens Protection Devices Limited
2.10 67/67N Directional Overcurrent & Earth Fault
2.10.1 Reference
Parameter
Value
θ
s
Angle setting
-95…+95
°
I
Applied current
In
V
Applied voltage
110 V phase-phase (63.5 V phase-earth)
2.10.2 Operate Angle
Attribute
Value
CA
Characteristic angle (I with respect
to V)
θ
s
,
±
5
°
Operating angle
forward
CA
- 85
° ±
5
°
to
CA
+ 85
° ±
5
°
reverse
(
CA
- 180
°
) - 85
° ±
5
°
to (
CA
- 180
°
) + 85
° ±
5
°
Variation in
characteristic
angle
10°C to +55°C
±
5
°
f
nom
± 5 %
±
5
°
2.10.3 Operate Threshold
Attribute
Value
Minimum levels for
operation
I (p/f)
> 5 % In
I (e/f)
> 10 % In
V (p/f)
> 1 V
V (e/f)
> 1 V
2.10.4 Operate and Reset Time
Attribute
Value
Operate time
typically 32 < 40 ms at characteristic angle + element
operate time
Reset time
typically < 65 ms at characteristic angle
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...