Chapter 4 - 7SR181 Solkor · Data Communications Definitions
© 2016 Siemens Protection Devices Limited
Chapter 4 - Page 45 of 80
OBJECT
REQUEST
(Library will parse)
RESPONSE
(Library will respond with)
Object
Number
Variation
Description
Function Codes
(dec)
Qualifier Codes
(hex)
Function
Codes
(dec)
Qualifier Codes
(hex)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
10
1
Binary Output
2 (write)
00, 01 (start-stop)
10
2 (default -
see note 1)
Binary Output
Status
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
11
0
Binary Output Change
- Any Variation
1 (read)
06 (no range, or all)
07, 08 (limited qty)
11
1
Binary Output Change
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
11
2 (default -
see note 1)
Binary Output Change
with Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
12
0
Control Relay
Output Block
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
12
1
Control Relay
Output Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
17, 28 (index)
129
(response)
echo of request
12
2
Pattern Control
Block
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
7 (limited quantity)
129
(response)
echo of request
12
3
Pattern Mask
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, noack)
00, 01 (start-stop)
129
(response)
echo of request
13
0
Binary Output
Command Event
- Any Variation
1 (read)
06 (no range, or all)
07, 08 (limited qty)
13
1 (default -
see note 1)
Binary Output
Command Event
without Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
13
2
Binary Output
Command Event
with Time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129
(response)
130
(unsol. resp)
17, 28 (index)
1 (read)
22 (assign class)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
20
0
Binary Counter
- Any Variation
7 (freeze)
8 (freeze noack)
9 (freeze clear)
10 (frz. cl. noack)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
20
1
32-Bit Binary Counter
(with Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
20
2
16-Bit Binary Counter
(with Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
20
3
32-Bit Delta Counter
(with Flag)
20
4
16-Bit Delta Counter
(with Flag)
20
5 (default
see note 1)
32-Bit Binary Counter
(without Flag)
1 (read)
00, 01 (start-stop)
06 (no range, or all)
07, 08 (limited qty)
17, 27, 28 (index)
129
(response)
00, 01 (start-stop)
17, 28 (index
- see note 2)
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...