Chapter 4 - 7SR181 Solkor · Data Communications Definitions
© 2016 Siemens Protection Devices Limited
Chapter 4 - Page 67 of 80
Analog Inputs
Static (Steady-State) Object Number: 30
Change Event Object Number: 32
Analog Input Deadband: 34
Static Variation reported when variation 0 requested: 1 (32-Bit Analog Input with Flag)
or 2 (16-Bit Analog Input with Flag)
or 3 (32-Bit Analog Input w/o Flag)
or 4 (16-Bit Analog Input w/o Flag)
or 5 (Single Precision, floating point Analog Input with Flag)
Change Event Variation reported when variation 0 requested: 1 (32-Bit Analog Change Event w/o Time)
or 2 (16-Bit Analog Input w/o Time)
or 3 (32-Bit Analog Input with Time)
or 4 (16-Bit Analog Input with Time)
or 5 (Single Precision, floating point Analog Input w/o Time)
or 7 (Single Precision, floating point Analog Input with Time)
Analog Input Reporting Deadband Variation reported when variation 0 requested: 1 (16-Bit)
or 2 (32-Bit)
or 3 (Single Precision, floating point)
Point
Index
Description
Default
Change Event
Assigned Class
(1, 2, 3 or none)
Default
Variation
Static
Object 30
Default
Variation
Event
Object 32
Default
Multiplier
Default
Deadband
368 Line Ib
0,3
2
4
100.000
0.100
369 Line Ic
0,3
2
4
100.000
0.100
370 Relay Ia
0,3
2
4
100.000
0.100
371 Relay Ib
0,3
2
4
100.000
0.100
372 Relay Ic
0,3
2
4
100.000
0.100
373 Remote Line Ia
0,3
2
4
100.000
0.100
374 Remote Line Ib
0,3
2
4
100.000
0.100
375 Remote Line Ic
0,3
2
4
100.000
0.100
376 Remote Relay Ia
0,3
2
4
100.000
0.100
377 Remote Relay Ib
0,3
2
4
100.000
0.100
378 Remote Relay Ic
0,3
2
4
100.000
0.100
379 Operate Ia
0,3
1
3
100.000
0.100
380 Operate Ib
0,3
1
3
100.000
0.100
381 Operate Ic
0,3
1
3
100.000
0.100
382 Restrain Ia
0,3
1
3
100.000
0.100
383 Restrain Ib
0,3
1
3
100.000
0.100
384 Restrain Ic
0,3
1
3
100.000
0.100
5.4 Additional Settings
The following relay settings are provided for configuration of the DNP 3.0 implementation when available and are
common to all ports using this protocol.
Setting Name
Range/Options
Default
Setting
Notes
Unsolicited
Mode
DISABLED, ENABLED
DISABLED
As Required
Setting is only visible
when any port
Protocol is set to
DNP3.
Destination
Address
0 - 65534
0
As Required
Setting is only
visible when DNP3
Unsolicited Events
set to Enabled.
DNP3
Application
Timeout
5, 6 ... 299, 300
10s
As Required
Setting is only visible
when any port
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...