4.3 CT Formulae P Class CTs
Example. For 5P20 15 VA CT: -
Knee point Vk (1 A) = VA x A.L.F + (R
CT
x A.L.F. x I
n
) = 15 x 20 + (0.05 x 20 x 1) = 301 V
In
1
Knee point Vk (5 A) = VA x A.L.F + (R
CT
x A.L.F. x I
n
) = 15 x 20 + (0.01 x 20 x 5) = 61 V
In
5
If the R
CT
is not known the second term i.e. (R
CT
x A.L.F. x I
n
) can be ignored as this term would be a low value.
CT ratio selection would typically be: -
e.g. I
fmax
=
50000 = 2500:1
ALF
20
A ALF of 20 means the CT is accurate to 20 x the primary CT current i.e. 20 x 2500 = 50000
e.g. I
fmax
=
25000 = 1250:1
ALF
20
Select a ratio of 1500:1 from Standard CT Series.
A ALF of 20 means the CT is accurate to 20 x the primary CT current i.e. 20 x 1500 = 30000
Alternately for 5P20 15 VA System CT: -
Knee point Vk (1 A) = A.L.F x I
sec
x (R
Relay
+ VA ) = 20 x 1 x (0.05 + 15 ) = 301 V
(I
sec
)
2
1
Knee point Vk (5 A) = A.L.F x I
sec
x (R
Relay
+ VA ) = 20 x 5 x (0.01 + 15 ) = 61 V
(I
sec
)
2
25
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...