7SR18 Commissioning & Maintenance Guide
Unrestricted ©2018 Siemens Protection Devices Limited
Page
15 of
Figure 2.3-3 Secondary Injection
2.4
T
YPICAL RESULTS FOR TESTING
87BD
87BD I
NITIAL
S
ETTING
87BD 1
ST
B
IAS
S
LOPE
S
ETTING
B
IAS
C
URRENT
(
X
I
N
)
M
EASURED ON
A
MMETER
A1
0.00
1.00
1.50
2.00
2.50
Operate Current Measured on Ammeter A2
0.10
0.10
0.10
0.11
0.16
0.21
0.26
0.20
0.20
0.20
0.22
0.33
0.44
0.56
0.30
0.30
0.30
0.35
0.53
0.71
0.88
0.40
0.40
0.40
0.50
0.75
1.00
1.25
0.50
0.50
0.50
0.67
1.00
1.33
1.67
0.50
0.60
0.50
0.86
1.29
1.71
2.14
0.50
0.70
0.50
1.08
1.62
2.15
2.69
Selected Settings
Test Results
0.00
1.00
1.50
2.00
2.50
Phase A Pickup
Phase B Pickup
Phase C Pickup
2.5
D
IFFERENTIAL
H
IGHSET
87HS
Differential Highset can be tested by single-phase secondary current injection. These settings will usually be
higher than the continuous thermal rating of the relay current inputs and equipment or test procedure should be
arranged in such a way that the short-term thermal withstand of the relay current inputs is not exceeded during
testing. 50 % of relay setting current can be injected into each relay simultaneously to achieve a differential
current level of 100 % if test current is limited by test equipment capacity.
During testing the Operate current can be monitored on the relay in the Instruments menu.
Summary of Contents for 7SR18 Solkor
Page 1: ...Energy Management 7SR18 Solkor Line Differential Relay Reyrolle Protection Devices ...
Page 2: ...Siemens Protection Devices Limited 2 ...
Page 93: ...7SR18 Configuration Guide Unrestricted Page 12 of 12 2015 Siemens Protection Devices Limited ...
Page 221: ...7SR181 Solkor Technical Manual Chapter 4 Page 2 of 80 2016 Siemens Protection Devices Limited ...
Page 225: ...7SR181 Solkor Technical Manual Chapter 4 Page 6 of 80 2016 Siemens Protection Devices Limited ...